شناسه محصول: OKS_QQX7A

رله اشنایدر – مایکام P127

مشاهده محصول در وب سایت تولید کننده : MiCOM P127

مشاهده کاتالوگ

گارانتی سلامت فیزیکی
موجود در انبار
ضمانت اصالت کالا

موجود در انبار

ارسال توسط فروشگاه آنلاین کالاسان

توضیحات

range of product
MiCOM P127
device short name
P127
relay application
Feeder
protection type
Overcurrent ANSI code: 50/51
Recloser ANSI code: 79
Cold load pick-up
Earth fault ANSI code: 50G/51G
Lockout ANSI code: 86
Negative sequence overvoltage ANSI code: 47
Undervoltage ANSI code: 27
Overvoltage ANSI code: 59
Rate of change of frequency ANSI code: 81R
Neutral voltage displacement ANSI code: 59N
Thermal overload protection ANSI code: 49RMS
Underfrequency ANSI code: 81L
Phase undercurrent ANSI code: 37
Breaker failure ANSI code: 50BF
Negative sequence overcurrent ANSI code: 46
Restricted earth fault ANSI code: 64REF
Directional earth fault ANSI code: 67N
Directional phase overcurrent ANSI code: 67
Overfrequency ANSI code: 81O
Voltage-restrained overcurrent ANSI code: 50V/51V
number of inputs
۴ current input CT…X/5 A and X/1 A
۳ voltage
۱۲ discrete
number of outputs
۹ discrete
communication port protocol
DNP3
IEC 60870-5-103
Modbus RTU
Complementary
[Us] rated supply voltage
۲۴٫٫٫۲۵۰ V DC 19.2…۳۰۰ V
۴۸٫٫٫۲۵۰ V DC 38.4…۳۰۰ V
۴۸٫٫٫۲۴۰ V AC 38.4…۲۶۴ V
control and monitoring type
Circuit breaker/contactor control
network and machine diagnosis type
Fault recording
Event recording
Disturbance recording15 s
switchgear diagnosis type
CT/VT supervision
Trip circuit supervision ANSI code: TCS
display type
Backlit LCD: 2 lines of 16 characters
discrete input voltage
۲۴٫٫٫۲۵۰ V DC 19.2 V standard variant
۴۸٫٫٫۲۵۰ V AC 19.2 V standard variant
۴۸٫٫٫۲۵۰ V DC 105 V further option
۴۸٫٫٫۲۵۰ V DC 77 V further option
۴۸٫٫٫۲۵۰ V DC 154 V further option
۴۸٫٫٫۲۴۰ V AC 105 V further option
۴۸٫٫٫۲۴۰ V AC 77 V further option
۴۸٫٫٫۲۴۰ V AC 154 V further option
communication port support
RS232
RS485
Environment
type of measurement
Current
height
۱۷۷ mm total:
۱۵۶ mm embedded:
width
۱۵۵ mm
depth
۲۴۹٫۶ mm total:
۲۲۳ mm embedded:
device mounting
Flush

 

جدول Cortec رله مایکام P127 – MiCOM – Cortec-P127

 

MiCOM P127
Ready-to-use configuration













P12x Overcurrent protection P12 7














Variant




Directional/non-directional three phase overcurrent and directional/non-directional earth fault relay 7



Earth current input



0.1 to 40 Ion A

0.01 to 8 Ion B

0.002 to 1 Ion C

Voltage input

57 – 130 V A

220 – 480 V B

Optional features



None 0

Additional 5 digital inputs 1) 1

IRIG-B inputs + additional 2nd rear port 1) 2

IRIG-B inputs + additional 2nd rear port + additional 5 digital inputs 1) 3

Measurement CTs 8) 4

Measurement CTs + additional 5 digital inputs 8) 5

Measurement CTs + IRIG-B input + additional 2nd rear port 8) 6

Measurement CTs + IRIG-B input + additional 2nd rear port + additional 5 digital inputs 8)
7

Auxiliary voltage Digital input voltage

48 – 250 Vdc / 48 – 240 Vac 105 – 145 Vdc (special application) H

48 – 250 Vdc / 48 – 240 Vac 24 – 250 Vdc T

48 – 250 Vdc / 48 – 240 Vac 110 Vdc -30% / +20% (special application) V

48 – 250 Vdc / 48 – 240 Vac 220 Vdc -30% / +20% (special application) W

24 – 250 Vdc / 48 – 240 Vac 24 – 250 Vdc / 24 – 240 Vac Z

Communication interface

MODBUS / MODBUS (if 2nd RS485 available)









1




KBUS / COURIER / MODBUS – not available 3) 2

IEC60870-5-103 / MODBUS (if 2nd RS485 available) 3

DNP3 / MODBUS (if 2nd RS485 available) 4) 4

IEC60870-5-103 / IEC60870-5-103 (if 2nd RS485 available) 9) 5

Modbus TCP/IP / Modbus (if 2nd RS485 available) 10) (with voltage V&W only) 6

IEC60870-5-103 Eth / Modbus (if 2nd RS485 available) 10) (with voltage V&W only) 7

Language

French
0

English / American
1

Spanish
2

German
3

Italian
4

Russian
5

Polish
6

Portuguese
7

Dutch
8

Czech
A

Hungarian
B

Greek 3)
C

Turkish 5)
E

Chinese 6)
D

Platform



SE look&feel Phase 2

2

SE look&feel Phase 2 with larger LCD

3

Latest Major Software release



V ?.? ?
Latest Minor Software release
V ?.? ?
Mounting option
None (default) 7) 0
Pre-fixed HMI (no withdrawability) 1
Sealed Cover 7) 2
Pre-fixed HMI + Sealed Cover 3
NOTES :
1) Only available with Phase 2 Hardware and V11.C , or later, firmware
3) Not available
4) Only available with software version V11, or later, firmware
5) Only available with software version V11.B, or later, firmware
6) Only available with Phase 2 Hardware with larger LCD
7) Not available with Auxiliary voltage/Digital input voltage code T
8) Only available with larger LCD and V14.A , or later, firmware
9) Only available with additional 2nd rear port (RS485)
10) For China only. Inquiry out of China, please contact product manager before tendering

نقد و بررسی‌ها

درمورد این محصول دیدگاه درج کنید.

هنوز بررسی‌ای ثبت نشده است.